22 Mar 2016  | Samuel Kerem

Share this page with your friends

This design idea illustrates how to keep telecom equipment operational during a short brownout. You must first understand a few details regarding the power supply for telecom equipment. The common voltage of the power source that feeds telecom equipment is –48V, although the actual voltage can range from –42.5 to –56V, –40 to –60V, or even beyond. The common power-"brick" dc/dc converter operates over the –36 to –75V range. A brownout occurs when the –48V source drops to 0V and stays there as long as 10 msec.

Using capacitive storage that connects to the brick's input is an obvious approach to overcoming this problem, but a shortcoming becomes apparent when you understand the reality of the –48V supply. For example the energy in a capacitor charged to voltage is (C×V2)/2, where C is the capacitance and V is the voltage. The brick stops its operation when the capacitor discharges to 36V. In general, the energy available to support the brick's operation is, therefore:



where V1 and V2 are the beginning and final –36V voltages, respectively, and U is the energy. Also, U=P×t, where P is power and t is time. Using these equations, you can find the time that the equipment will stay operational:



or, to define the capacitor's value:



Assume that the brownout occurs when the voltage at the brick's input is –39V, which is the case when –48V is –40V but the brick loses at least 1V because of protective ORed diodes in a hot-swap configuration. Also, assume that the storage capacitor charges to –39V. The equipment operates until this storage capacitor discharges to –36V. Assume that the equipment consumes 100W. To store enough energy for 5 msec, the capacitor's value would have to be approximately 4500µF. The capacitor must be rated for the maximum possible incoming voltage, which can be more than 75V, so the minimum rating of 100V is a must. The 4500-µF, 100V capacitor is a sizable part. If the design requires twice as much operational time at a power consumption of 300W, the capacitor must have a value of 27,000µF and 100V.


Figure: Charged to double the input voltage, the energy stored in capacitor C1 dumps into the input of the "brick" power supply during brownouts when the input voltage drops to less than 237V.


This Design Idea still requires a capacitor, but the capacitor has a lower value—that is, 200µF versus 4500µF—and sustains 100W during a 5-msec brownout. This approach increases reliability and reduces cost and size. The hidden feature is the power brick's ability to stay operational over the input range of –36 to –75V and even to operate under surges greater than –80V. The figure shows how you can use this feature. The figure depicts a positive input voltage. The brick is isolated, so polarity is irrelevant, but positive interpretation is easier to illustrate.

Remember that the stored energy in the capacitor grows exponentially, whereas the capacitor's voltage increases linearly. The doubler charges C1 to twice the input voltage or at least to 80V. Even if, hypothetically, you expect a 5-msec brownout as often as 10 sec, the current to charge 200µF is still only approximately 3 mA. The comparator watches the input voltage, and, as soon as it drops below 37V, switch S1 closes, and the energy from C1 discharges to the power brick.


About the author
Samuel Kerem contributed this article.


This article is a Design Idea selected for re-publication by the editors. It was first published on May 15, 2008 in EDN.com.




Want to more of this to be delivered to you for FREE?

Subscribe to EDN Asia alerts and receive the latest design ideas and product news in your inbox.

Got to make sure you're not a robot. Please enter the code displayed on the right.

Time to activate your subscription - it's easy!

We have sent an activate request to your registerd e-email. Simply click on the link to activate your subscription.

We're doing this to protect your privacy and ensure you successfully receive your e-mail alerts.


Add New Comment
Visitor (To avoid code verification, simply login or register with us. It is fast and free!)
*Verify code:
Tech Impact

Regional Roundup
Control this smart glass with the blink of an eye
K-Glass 2 detects users' eye movements to point the cursor to recognise computer icons or objects in the Internet, and uses winks for commands. The researchers call this interface the "i-Mouse."

GlobalFoundries extends grants to Singapore students
ARM, Tencent Games team up to improve mobile gaming


News | Products | Design Features | Regional Roundup | Tech Impact